Types of Orifice Meters: Concentric, Eccentric & Segmental Explained
An orifice flow sensor is not one part. It is a small team: a plate, taps, a transmitter, and a signal path. Miss one player, and the whole relay race ends with a dropped baton. This guide walks through every part of the loop, so EHS buyers

An orifice flow sensor is not one part. It is a small team: a plate, taps, a transmitter, and a signal path. Miss one player, and the whole relay race ends with a dropped baton.
This guide walks through every part of the loop, so EHS buyers, EPC contractors, and plant engineers know what to specify before ordering an orifice flow sensor.
What Is an Orifice Flow Sensor?
An orifice flow sensor is a loose industry term for an orifice plate paired with a differential pressure (DP) transmitter. Together, they sense flow from the pressure drop across the plate.
Vendors usually call these orifice meters or DP flow meters, so search both terms when you compare quotes. A bare plate gives you no signal. It needs the rest of the loop.
The orifice meter working principle is short:
- The orifice restriction speeds up the fluid.
- Pressure drops just after the plate.
- Taps pick up the difference, and a transmitter turns it into a signal.
One fact explains why range matters. Pressure drop rises with the square of flow, says Automation.com. The ISA Handbook of Measurement Equations and Tables adds that DP across an orifice is used more than any other type of flow measurement.
What Are the Components of a Complete Orifice Flow Sensor Loop?
A complete loop has six parts, from the plate to the control room. Each one has a job, and each one can fail quietly.
|
Part |
Its job |
What to check |
|
Orifice plate |
Creates the pressure drop |
Material, bore, edge quality |
|
Plate holder and taps |
Holds the plate and picks up pressure |
Tap style: flange, corner, or D and D/2 (ISO 5167-2) |
|
Straight meter run |
Gives a smooth flow profile |
Length for your beta ratio and fittings |
|
Impulse lines and manifold |
Carry pressure to the transmitter. |
Layout, valves, slope |
|
DP transmitter |
Converts pressure difference to a signal |
Range matches the sizing sheet. |
|
DCS or flow computer |
Shows and records flow |
Square root and compensation set correctly |
A few notes on the table:
- A 3-valve manifold is standard on many setups. ABB lists a 5-valve option, too.
- The straight run is commonly cited as 25 pipe diameters upstream and 10 downstream. Confirm the exact figure for your layout.
- The transmitter is what many people mean by an orifice-type flow transmitter. A flow transmitter orifice plate pair only works if both share one sizing sheet.
Remote or Integral: Which Orifice Flow Sensor Style Fits Your Line?
Remote mounting suits larger pipes. An integral or compact orifice flow sensor suits small lines, where it saves tubing and joints.
|
Factor |
Remote mount |
Integral (compact) mount |
|
Impulse tubing |
Needed |
Mostly removed |
|
Leak points |
More joints |
Fewer joints |
|
Typical line size |
Larger pipes |
Small lines |
|
Install effort |
More fittings |
One assembled unit |
Some facts back this up:
- An IMEKO conference paper says integral manifolds let you mount the transmitter directly on the sensing element, so impulse tubing and connectors are not needed.
- Emerson’s integral orifice meters target small lines of 0.5 to 1.5 inches (15 to 40 mm), and the self-centring plate prevents installation errors.
- ABB describes its compact unit as a DP flow system pressure-tested as an assembly.
- E2G lists about 1% uncertainty and a 316 stainless steel plate for integral orifice units.
Does an Orifice Flow Sensor Need Pressure and Temperature Compensation?
For gas and steam, usually yes. Density changes with pressure and temperature, so a DP-only reading can mislead you on mass flow.
A multivariable transmitter measures DP, static pressure, and temperature together. Then it calculates mass flow on its own. Emerson says this removes the need for a separate computer or control system to do the math.
- Gas and steam: compensation matters most.
- Stable liquids: Emerson notes most do not need line pressure and temperature compensation.
- Accuracy gain: an orifice setup gives roughly 1% to 5% basic and 0.5% to 1.5% with compensation, per Pumps & Systems.
- Range gain: the IMEKO paper cites ±0.75% of mass flow over an 8:1 range for an integral orifice with a multivariable transmitter. That is a vendor-leaning source, so verify with your supplier.
How Does an Orifice Flow Sensor Compare With a Venturi?
An orifice costs less but wastes more pressure. A venturi handles a wider range but costs more.
- Orifice: turndown about 3:1 to 5:1, and permanent pressure loss near two-thirds of the measured DP (Automation.com).
- Venturi: turns down to 10:1 and lower pressure loss (EngineerExcel).
When you compare an orifice and venturi meter for a pump line, count the energy cost too.
What Mistakes Break an Orifice Flow Sensor Loop?
Most faults hide in the impulse lines, not the plate. Here are the usual suspects:
- Wrong layout: Aivon advises gas taps on the upper half of the pipe with the transmitter above, and liquid taps on the lower half with the transmitter below.
- Trapped gas bubble: it can shift a liquid reading even when the process has not changed (ICS Schneider).
- Freezing: ice in cold outdoor lines can rupture the transmitter diaphragm, so plants use heat tracing (Process & Instrumentation).
- Worn edge: even slight erosion can hurt accuracy (Automation.com).
- Wrong plate for the fluid: dirty or two-phase fluids may need an eccentric or segmental orifice plate type.
What Should EHS and EPC Teams Check Before Ordering an Orifice Flow Sensor?
Check the full loop, not just the plate. A good plate with a mismatched transmitter is still a bad buy.
- Sizing sheet shared by plate and transmitter supplier
- Standard named on the datasheet, such as ISO 5167-2
- Hazardous area approvals for the transmitter, if needed
- Safety rating, if the loop sits in a safety function. Emerson’s integral orifice meter, for example, lists SIL 2/3 certification to IEC 61508 by a third party
- Diagnostics such as plugged impulse line detection are offered on some models
- Plate inspection plan: one industry guide suggests about every 5 years in clean service and every 1 to 2 years in erosive service
FAQs
1. What is an orifice flow sensor?
It is an orifice plate paired with a DP transmitter that senses flow from the pressure drop.
2. How does an orifice flow sensor work?
Fluid speeds up through the hole, pressure drops, and the transmitter turns that drop into a flow signal.
3. What is the difference between an orifice plate and an orifice-type flow transmitter?
The plate creates the pressure drop, and the transmitter reads it and sends the signal.
4. Do gas and steam lines need a multivariable transmitter?
Usually yes, because it measures DP, pressure, and temperature together for mass flow.
5. What are the types of orifice flow meters?
They come as remote-mount or integral units, with concentric, eccentric, or segmental plates.
6. How accurate is orifice meter flow measurement?
About 1% to 5% for a basic setup and 0.5% to 1.5% with compensation, per Pumps & Systems.
Ready to Build Your Loop?